Envoy Installation and Operation
2014 Enphase Energy Inc. 141-00011 Rev 05
56
Message Shown on
Events and Inventory
Screens
Description
DC Voltage Too High
Recommended Action: Ask your installer to check that the PV module and
microinverter are compatible. It may be that the PV module generates a higher
voltage than is recommended for the microinverter. The Enphase M250 and M215
are compatible with most 60-cell modules. The M190 and D380 are compatible
with many 60- and 72-cell modules.
Description: The microinverter reports that DC input voltage from the PV module
is too high.
If the condition persists: If the PV module is compatible and the condition
persists, contact your installer or refer to the Troubleshooting Guide at
http://www.enphase.com/support.
DC Voltage Too Low
Recommended Action: This is usually a normal condition during hours of low light
and at dawn and dusk.
Description: The microinverter reports that DC input voltage from the PV module
is too low. If this condition does not clear during hours of full daylight, the
microinverters may be heavily shaded or covered by snow.
If the condition persists: If this event occurs during full daylight or if the condition
persists, contact your installer or refer to the Troubleshooting Guide at
http://www.enphase.com/support.
If this event occurs and clears daily or often during hours of full daylight, check that
the PV module and microinverter are compatible. The M215 and M250 are
compatible with most 60-cell modules.
Download to module
begun
Description: The Envoy has started a software upgrade to the indicated
microinverter.
Recommended Action: This process may take a few minutes. No action is
required.
Download to module
ended
Description: The Envoy has successfully delivered a software upgrade to a
microinverter.
Recommended Action: No action is required.
Download to module
failed
Description: The Envoy was unable to successfully deliver a software upgrade to
a microinverter.
Recommended Action: No action is required; the Envoy will repeat the attempt.
Envoy Failure
Recommended Action: Unplug the Envoy from the AC outlet and plug it in once
again. Leave it plugged in and in place for at least 15 minutes.
Description: This message displays after the Envoy has tried unsuccessfully three
times to start up.
This condition does not affect your system’s ability to produce power. When the
connection is restored, the Envoy will catch up with the transmission of any/all
energy data it has stored.
If the condition persists: If the Envoy continues to display Gateway (or Envoy)
Failure or if it never moves beyond the Initialization stage, contact your installer or
refer to the Troubleshooting Guide at http://www.enphase.com/support.
Filesystem integrity audit
failed
Description: The Envoy file system integrity audit has failed.
Recommended Action: For assistance, contact Enphase Energy customer
support.

Table of Contents

Other manuals for enphase Envoy

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the enphase Envoy and is the answer not in the manual?

enphase Envoy Specifications

General IconGeneral
ModelEnvoy
CategoryGateway
CompatibilityEnphase Microinverters
CommunicationWi-Fi, Ethernet
NetworkingIEEE 802.11 b/g/n
Operating Temperature-40°C to +65°C
Enclosure RatingIP30
Power Supply100-240 VAC
Power Consumption5W typical

Related product manuals