User Manual
4 Controller
22
EMW90HDNC1U Air-cooled Chiller
Parameter Default Value Setting Range Unit Description
Control Temp Monitor Temp
Monitor Temp
Sup Water
-
Identifies the type of
temperature controlled by the
system.
Monitor Temp: The system
controls according to the
outlet coolant temperature.
Sup Water: The system
controls according to the cell
temperature sent by the host
computer during
communication.
The default values and value ranges of the above parameters are for reference only, and the factory settings shall prevail.
(Optional) Team Setting
When supporting the group control function, the operator
must make the relevant group control setting after the
chiller is powered on for the first time and runs normally,
otherwise the group control function will not be realized,
and the chiller will return to the independent operation
control mode.
Lorsqu'il est équipé de la fonction de contrôle de groupe,
l'opérateur doit effectuer les réglages de contrôle de
groupe pertinents après que le refroidisseur ait été mis
sous tension et ait fonctionné normalement pour la
première fois, sinon la fonction de contrôle de groupe ne
sera pas réalisée et le refroidisseur reviendra au mode de
contrôle de fonctionnement indépendant.
Group control can improve the efficiency of
chillers and avoid the competition between
chillers by cascading multiple chillers.
Group control function is an optional function.
When the group control function is not provided,
the values of the parameters in the Team Setting
interface are displayed as "****", as shown in
Figure 4-15.
Figure 4-15 Team Setting interface
When the chiller provides group control function,
you can refer to Table 4-3 for parameter setting.
Table 4-3 Parameter description of the Team
Setting interface
Parameter Description
Team
Set to Team when supporting
group control function.
Local Addr
The address of this machine
and the address of the main
control unit are configured as 1.
If the number of group control
units is 2, that is, when two
chillers back up each other, the
local address is configured as 1,
and the other backup unit
address is configured as
2
.
Mode Set to Auto.