? Fault code A. and 4 flash alternately and the
light is red?
Burner fan continues to operate when the burner
control unit is in idle state.
! Wiring fault.
Check whether the wiring from plugX21 to the
burner fan has continuity.
! A vacuum is generated in the chimney due to
strong wind and this affects the burner fan.
? Fault code A. and 5 flash alternately?
The burner fan does not reach the required speed
when starting up.
! The air route is blocked.
Check the air supply route.
! This air filter is not OK.
Check the air filter and clean it if necessary, see
page11 (Cleaning).
! Fan motor defective.
Check motor.
! Wiring fault.
Check wiring (plugs X21 andX12).
? Fault code A. and 5 flash alternately and the
light is red?
The fault could not be rectified. All start-up at-
tempts have been used and the burner control
unit goes into lock-out.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
Rectify the cause of the fault as described above
for warningF.5.
Check the air filter and replace it if necessary.
? Fault code A. and 6 flash alternately?
The burner fan does not reach the required speed
during operation.
! The air route is blocked.
Check the air supply route.
! This air filter is not OK.
Check the air filter and clean it if necessary, see
page11 (Cleaning).
! Fan motor defective.
Check motor.
! Wiring fault.
Check wiring (plugs X21 andX12).
? Fault code A. and 7 flash alternately?
! The air filter is becoming blocked and must be
cleaned shortly.
Check the air filter and clean it if necessary, see
page11 (Cleaning).
? Fault code A. and 8 flash alternately?
The main fan does not start during the start-up
attempts.
! The pressure switch does not switch.
Check the air hose on the pressure switch for
dirt and moisture and clean it.
Check the pressure switch and replace it if nec-
essary.
! The main fan is rotating in the wrong direction.
Check the wiring. The rotating field may be incor-
rect. Swap L1 and L2, see page4 (Wiring).
! Main fan defective.
If possible, remove the main fan and replace it.
? Fault code A. and 8 flash alternately and the
light is red?
The fault could not be rectified. All start-up at-
tempts have been used and the burner control
unit goes into lock-out.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
Rectify the cause of the fault as described above
for warningA.8.