Check the cable connection, cable and plug for
damage or moisture. The plug must be fitted
correctly.
Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.
The ionization electrode is defective and must
be replaced.
! Air in the gas pipe.
Vent the gas pipe.
! Valves do not open.
Disconnect the valve plug on the gas combina-
tion control and measure the voltage at the valve
plug during the safety time.
If the voltage is not adequate, first check fuseF2
(4A). If the display and the LEDs are not lit, it is
defective.
If the voltage is not adequate, replace the gas
combination control and return it to the supplier.
? Fault code F. and 1 flash alternately and the
light is red?
The fault could not be rectified. All start-up at-
tempts have been used and the burner control
unit goes into lock-out.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
Rectify the cause of the fault as described above
for warningF.1.
? Fault code F. and 2 flash alternately?
The flame has gone out during operation. If a
restart has been programmed, an automatic
restart will be completed.
! Poor flame signal due to incorrect burner adjust-
ment.
Readjust the CO
2
value, see page9 (Adjust-
ing the heater).
! Poor flame signal due to dirty or badly connected
ionization electrode.
Check the ionization electrode and clean it with
fine abrasive paper if necessary.
Check the cable connection, cable and plug for
damage or moisture. The plug must be fitted
correctly.
Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.
The ionization electrode is defective and must
be replaced.
? Fault code F. and 2 flash alternately and the
light is red?
The fault could not be rectified. All start-up at-
tempts have been used and the burner control
unit goes into lock-out.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
Rectify the cause of the fault as described above
for warningF.2.
? Fault code F. and 3 flash alternately?
The burner control unit detects a flame signal
during start-up or in fault status.
! Incorrect flame signal due to leakage/creepage
current.
Check the wiring, see page4 (Wiring).
Check the ionization electrode.
! Incorrect flame signal through conductive ce-
ramic insulation, e.g. surge via PE wire, possible.
Remedy incorrect flame signal. Replace the
ionization electrode and, if necessary, also the
complete burner control unit and housing.
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
? Fault code A. and 3 flash alternately and the
light is red?
The fault could not be rectified after four auto-
matic start-up attempts. All start-up attempts
have been used and the burner control unit goes
into lock-out.
! This air filter is not OK.
Check the air filter and clean it if necessary, see
page11 (Cleaning).
Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.