MAGPRO16 Addressable Fire Alarm Panel Installation and Programming Manual
38
MAGPRO-R Module for 240V interface
Relay module with interface for 240 VAC. The module is available in
two versions with 1 and 2 relay outputs. Use the functional buttons to
set the following parameters:
(1) OUT 1 Set the parameters for the output see the description
of module MAGPRO-0i4O.
(2) ON/ OFF LED Press to switch on/ off the device LED.
(4) ON/ OFF LED BLINK Alternatively changes the status of the
device LED indication.
All set parameters are confirmed wit ENTER button. The exit to the main screen of DEVICE SETUP menu is with
pressing CANCEL button.
MAGPRO-GAS GAS Detector
MAGPRO-GAS is a gas detector designed for application in
addressable fire alarm systems with MAGPRO16/96 fire alarm
panels.
MAGPRO-GAS is designed for detection of leaking natural gas and
LPG. The detector is equipped with alarm output for management of
manipulator or electromagnetic valve (optional accessories).
Use the functional buttons to set the following parameters:
(2) ON/ OFF LED Press to switch on/ off the device LED.
(4) ON/ OFF SOUNDER If OFF option is set, the sounders in the system will not be activated in case of activation of
the gas detector. If ON option is set, the sounders in the system will be activated in case of activation of the gas
detector.
All set parameters are confirmed wit ENTER button. The exit to the main screen of DEVICE SETUP menu is with
pressing CANCEL button.
Table 2. Activation types Parameters Setting:
Activation type
Parameter Settings
Loop
No
Group
No
Zone
No
Alarm
No
Device
No
Input
No*
Logic
Behavior
Device
1/2
-
-
-
1 - 250
1 - 4
-
Latched/ Unlatched
Input group
-
1 - 16
-
-
-
-
AND/OR
Latched/ Unlatched
Fire zone
-
-
1 - 16
1-9
-
-
-
Latched
Fire zone group
-
1 - 16
-
-
-
-
AND/OR
Latched
FIRE (common)
-
-
-
-
-
-
-
Latched
Fault zone
-
-
1 - 16
-
-
-
-
Latched/ Unlatched
Fault zone group
-
1 - 16
-
-
-
-
AND/OR
Latched/ Unlatched
FAULT (common)
-
-
-
-
-
-
-
Latched/ Unlatched
Fault system
-
-
-
-
-
-
-
Latched/ Unlatched
Pre alarm zone
-
-
1 - 16
-
-
-
-
Latched/ Unlatched
DISABLE (common)
-
-
-
-
-
-
-
Latched/ Unlatched
Sounder on
-
-
-
-
-
-
-
Latched/ Unlatched
Reset
-
-
-
-
-
-
-
Unlatched
Evacuate
-
-
-
-
-
-
-
Latched
Silence buzzer
-
-
-
-
-
-
-
Latched/ Unlatched
Silence alarm
-
-
-
-
-
-
-
Latched/ Unlatched
Test
-
-
-
-
-
-
-
Latched/ Unlatched
* For input/ output module only.