Programming
Using the CMDN Configuration Program
Overview
The CMDN configuration program is used to configure the annunciator
operating mode as: Class A or B IRC-3 (FCC/PCPU) data line mode;
Class A or B FCC mode; or Class B LSS4 mode.
For each operating mode, the configuration of one or more
annunciators is a three phase process:
Phase 1 (the "Parameter Entry for Entire Project” screen) configures
the overall life safety remote annunciator network;
Phase 2 (the "Parameter Entry for Selected Display" screen)
configures an individual annunciator;
Phase 3 (the "Message Entry/Editing for Selected Display" screen)
enters and edits individual annunciator messages.
Copies of the LSRA worksheets at the end of this document should be
filled-in to assist you in rapidly entering annunciator information.
Starting the Configuration Program
Start the LSRA configuration program by typing:
CD\CMDN
CMDN
The opening screen, shown below, requests a 1 to 8 character project
name, which is used as the filename for all files relating to this project.
If a project name has been previously entered, typing in the project
name will open its files, and the next two steps will be skipped.
Remote Alpha-Numeric Display Network
PROJECT SELECTION
Enter Project Name : _________
Project Name: (8 char max) is used to identify a specific project.
Alphanumeric characters - no spaces.
Project Description: (20 char max) provides a description of the project.
Type: defines the fire panel model associated with this project.
The first time a filename has been entered, a project description may be
entered. This information appears on all project configuration reports.
Press the ENTER key to bypass this step. The project description
screen follows:
4.4
LSRA Installation, Operation, Maintenance, and Configuration Manual
firealarmresources.com