Programming
PRINTER BAUD 9600 ; 2400, 4800, 9600
MSG ROUTE ALL ; ALARM, SUPERVISOR, TROUBLE, ALL
SWITCH MASK FF ; [0][0] - [F][F] [ ENABLE ][ DISABLED ]
ERROR ACTION 0001 ; 0001
ANNUNCIATION GLOBAL ; LOCAL - GLOBAL
EXTERNAL MSG INACTIVE ; ACTIVE - INACTIVE
; 0 1 2 3 4
; 01234567890123456789012345678901234567890
message 000101 LSS field point zone 01 ;
message 000102 LSS field point zone 02 ;
message 000103 LSS field point zone 03 ;
message 000104 LSS field point zone 04 ;
message 000105 LSS field point zone 05 ;
message 000106 LSS field point zone 06 ;
message 000107 LSS field point zone 07 ;
message 000108 LSS field point zone 08 ;
message 000109 LSS field point zone 09 ;
message 000110 LSS field point zone 10 ;
;:::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::
From the DOS prompt, type edit template.lss and press
ENTER. Repeat the Editing Steps through the downloading steps
presented in this section.
LSRA application for FCC system
; LSRA source file template for FCC LSRA application.
; Definition of commands
:
;
; MAX NODES - Establishes the number of networked displays.
; ANNUNCIATION - Selects weather a message must be defined locally
; to be annunciated. Selections include GLOBAL
; and LOCAL. Global will allow annunciation of
; messages regardless of weather they are defined
; locally or not.
; EXTERNAL MSG - Selects the FCC message propagation and caching
; system. To correctly utilize this function, the master
; LSRA must have EXTERNAL MSG set to ACTIVE
; as well as any LSRA that elects to use this option.
; FIRE SYSTEM - Must be set to either FCC A or FCC B for FCC
; operation.
; MSG ROUTE - The command allows the filtering of in-coming
; message. Selections include ALL, ALARM,
; SUPERVISORY and TROUBLE.
; NETWORK CLASS - Communications class. The number of RS485
; connections that will be utilized between LSRAs on
; the network. Selections include class A or B.
; NETWORK BAUD - The communications baud rate for the LSRA
; network.
; GEO - Determines display operations for given geographic
; area.
; PRINTER TYPE - Local printer selection.
; PRINTER BAUD - Selects baud rate at which to communicate with
4.36
LSRA Installation, Operation, Maintenance, and Configuration Manual