3 Installation page 21
ELC X-Series-V1.5-06.18-GB subject to technical alterations
3.2.13 X805 and X806: Control cables
Fig. 16 on page 24 shows the interconnection of X805 and X806. Comments on the wiring are
given in the following tables.
X806:
Connector pin assignment:
Connection torque:
min. 0.22 Nm
max. 0.25 Nm
Pin assignment X806:
Continuous contact, connected
to X805.1
Control signal input safety relay
+24V DC
Control signal (+24V DC ± 10%
/ 35mA) for the safety relay in
reference to X806.7 (GND)
Input initialisation signal for
safety shutdown +24Vext.
24V DC ± 10% external supply
in reference to X806.7 (GND)
Continuous contact, connected
to X805.4, usable for shield of
the control cable
Output 24V DC,
connected to X805.5
Short-time buffer voltage after
emergency shutdown/switch-
off
Capacitance 47mF +/-20% 24V
+/-10%
* 24V_USV available for certain ELC-types only