EasyManuals Logo

Evco EV3 CHIL User Manual

Evco EV3 CHIL
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
EVCO S.p.A. EV3 CHIL & EVD CHIL | Installer manual ver. 1.2 | Code 1443DCHILE124
page 36 of 46
AFLo
Flow alarm
This alarm is activated when the input configured as flow switch is active for a period of AL09, with a delay of AL08 from
pump switch-on; it is deactivated when the input is inactive for a time amounting to AL10.
It reverts to manual re-arm if the number of alarm events in an hour exceeds AL07.
Main results
- All functions switched off.
AHtr
High temperature alarm
This alarm is activated when the input water temperature exceeds Al15 for a period longer than Al16. It is deactivated
when the temperature is lower than Al15-Al13.
Main results
- Compressors switch off
EA01
EA02
EA03
EA04
Probe alarms
The alarm is activated in the following situations:
- when a probe short circuits or is interrupted
- if the upper or lower limits set for a probe are exceeded
Main results
- All functions switched off.

Other manuals for Evco EV3 CHIL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EV3 CHIL and is the answer not in the manual?

Evco EV3 CHIL Specifications

General IconGeneral
BrandEvco
ModelEV3 CHIL
CategoryController
LanguageEnglish

Related product manuals