EVCO S.p.A. EV3 CHIL & EVD CHIL | Installer manual ver. 1.2 | Code 1443DCHILE124
page 40 of 46
Operating humidity
EV3 CHIL
Relative humidity without condensate from 10 to 90%. EVD CHIL
EV3K01
Pollution status of the
control device
EV3 CHIL
2.
EVD CHIL
EV3K01
Operating altitude
EV3 CHIL
from 0 to 2,000m (from 0 to 6,591ft). EVD CHIL
EV3K01
Transport altitude
EV3 CHIL
From 0 to 3,048m (from 0 to 10,000ft). EVD CHIL
EV3K01
Environmental
compliance
EV3 CHIL
- RoHS 2011/65/EC
- WEEE 2012/19/EU
- REACH (EC) Regulation 1907/2006.
EVD CHIL
EV3K01
EMC compliance
EV3 CHIL
- EN 60730-1
- IEC 60730-1.
EVD CHIL
EV3K01
Power supply
EV3 CHIL
12VAC (±15%), 50/60 Hz (±3 Hz), max. 6VA not insulated, supplied by a class 2
circuit.
Protect the power supply with a 1 A-T 250V fuse.
EVD CHIL
115... 230VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 6VA insulated.
Protect the power supply with a 2 A-T 250V fuse.
EV3K01
- 12VAC (+10 % -15 %), 50/60 Hz (±3 Hz), max. 7VA not insulated.
- 12VDC (±15%), max. 5W not insulated, supplied by a class 2 circuit.
Protect the power supply with a 1 A-T 250V fuse.