Label Default Min. Max. U.M. Description
P10 60 0 100 % Fan speed setpoint economy setting
P11 40 0 100 % Fan speed setpoint night-time setting
P12 80 0 100 % Fan speed setpoint manual setting
P13 100 0 100 % Fan speed setpoint from digital input
P14 40 0 100 % Damper opening setpoint comfort setting
P15 30 0 100 % Damper opening setpoint economy setting
P16 20 0 100 % Damper opening setpoint night-time setting
P17 40 0 100 % Damper opening setpoint manual setting
CNF Configuration parameter menu
C01 30,0 0,0 40,0 °C Maximum temperature setpoint value in hot mode
C02 10,0 0,0 40,0 °C Minimum temperature setpoint value in hot mode
C03 30,0 0,0 40,0 °C Maximum temperature setpoint value in cold mode
C04 10,0 -0,0 40,0 °C Minimum temperature setpoint value in cold mode
C05 100 0 100 % Maximum fan setpoint value
C06 10 0 100 % Minimum fan setpoint value
C07 100 0 100 % Maximum damper setpoint value
C08 10 0 100 % Minimum damper setpoint value
C09 ON OFF ON Enable RTC
C10 0 0 255 Parameter reserved for supervisor use
C11 1 0 2
Change-over mode
0 = Manual
1 = Manual+Automatic
2 = Auto
C12 5 0 100 % Fan/damper control step
C13 1 0 100 s Increase/decrease fan/damper control time
C14 20 0 100 % Minimum fan value with compressor ON
C15 20 0 100 % Minimum fan value with 1 heater ON
C16 20 0 100 % Minimum fan value with 2 heaters ON
C17 5 0 255 s Post-ventilation from OFF
C18 -12 -127 127 Servicer password
C19 -123 -127 127 Manufacturer password
C20 3 0 5
Second display
0 = Hour
1 = Humidity
2 = Temperature setpoint
3 = External temperature
4 = Fan speed
5 = Fan pressure capacity/differential
C21 0 0 1
Sun LED meaning
0 = Heating