Psp 0.00 100.00 % - - - - User target position
EnaS 0 1 - - - - - - - - User
enable valve status
0 = valve not enabled
1 = valve enabled
ResS 0 1 - - - - - - - - User
resynchronization request status
0 = no request
1 = request reserved
IhoS 0 1 - - - - - - - - User
holding current status
0 = operating phase current
1 = holding phase current
Te - - - - - - - - °C - - - - User Te (evaporation temperature)
Pe - - - - - - - - barG - - - - User Pe (evaporation pressure)
Ts - - - - - - - - °C - - - - User Ts (suction temperature)
SH - - - - - - - - K - - - - User SH
SpSH - - - - - - - - K - - - - User SH setpoint
SetS 1 2 - - - - - - - - User selected SH parameters set
PidP - - - - - - - - % - - - - User PID setpoint position output
ParS 0 2 - - - - - - - - User
parameters status
bit0: disable the valve to accept new
parameters
bit1: reset the board to accept new
parameters
SRat - - - - - - - - step/s - - - - User actual value step rate
SetM - - - - - - - - K - - - - User SH setpoint SH with MOP correction
Upr - - - - - - - - - - - - - - - - User
used probes
b 0: AI1
b 0: AI2
b 0: AI3
b 0: AI4