Figure 11. Wireless network configuration example
6.2.3.2 OCPP Configuration
There are 2 standard parameters for back-end setting. Please get them from the back-end supplier.
-Charger ID
-OCPP Server End Url
Figure 12. Example from OCPP-J 1.6 spec
(Note: The protocol upper controller supports is OCPP-J 1.6, please refer to the OCPP official documents if you
have any question about the above 2 parameters or the protocol itself)
Connection Check
If the above settings are done properly, you should see the ‘ ’ icon on screen (without reboot).
Attention: as the OCPP is just one standard protocol, some customer private define contain is in it. So any
access to OCPP platform need to do test before true application.