EasyManuals Logo

Extreme Networks Virtual Services Platform 7200 Series User Manual

Extreme Networks Virtual Services Platform 7200 Series
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
No. Task Description
are missing, contact Extreme Networks
support.
7. Make sure that the power cord has the
correct country-specific termination.
See Power cord types and order codes on
page 14.
8. Prepare the rack. Ensure that there is enough rack space to
accommodate a 1RU switch (4.45 cm).
Ensure that the rack is bolted to the floor and
braced if necessary.
Ensure that the rack is grounded to the same
grounding electrode used by the power service
in the area. The ground path must be
permanent and must not exceed 1 Ohm of
resistance from the rack to the grounding
electrode.
March 2020 Installing the VSP 7200 Series 17

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Extreme Networks Virtual Services Platform 7200 Series and is the answer not in the manual?

Extreme Networks Virtual Services Platform 7200 Series Specifications

General IconGeneral
BrandExtreme Networks
ModelVirtual Services Platform 7200 Series
CategorySwitch
LanguageEnglish

Related product manuals