B680H 12 732719 - Rev.D
Translation of the original instructions
ENGLISH
Display
Function Default
S2
Loop 2 sensitivity
Adjusts the sensitivity of the vehicle detection
loop
00 Minimum sensitivity
10 Maximum sensitivity
05
Mt
Motor movement
Using the function provided by this parameter
makes it possible to manually move the barrier
bar, operating as dead-man. Pressing + will
open the automated system, pressing - causes
the automated system to close.
oP pressing +, open
cL pressing -, close
--
tL
Learning
Working time and limit switch learning (see
section 7.2)
--
St
AUTOMATED SYSTEM STATUS:
This allows you to choose whether to quit the programme
and save the data.
Y = quit and save the data
no = quit without saving the data
On quitting the programme, press the F key to display the
status of the automated system
00 Beam closed
01 Beam open
02 Stationary ready to open
03 Stationary ready to close
04 Automated system paused
05 Opening
06 Closing
07 Failsafe in progress
08 2-EASY device verification in progress
09 Pre-flashing then OPENS
10 Pre-flashing then CLOSES
11 EMERGENCY Open
You can go to St at any time by simultaneously pres-
sing F and -.
Displaying of the automated system status
St is extremely
important for the installing/maintenance technician in order
to distinguish the logical processes that the board carries out
during movement.
If, for example, the automated system status is CLOSED, the
display MUST read
00. When the OPEN command is received,
the display will change to
09, if pre-fl ashing is enabled, or
directly to
05 (the OPENING movement) to then display 01
once the position of gate OPEN is reached).
Example of a status sequence displayed starting from a closed barrier
The sequence does not include statuses
09 and 10 which
correspond to pre-flashing when opening and closing,
respectively.
5.2 Changing the predefi ned parameters set
The E680 board features six sets of pre-defined configurations that
allow rapid adapting to the size of the beam installed, making it the
starting point for a fine adjustment of the parameters.
To select one of the available configurations, it is necessary to change
the parameter
cF from the default value of 06 to that corresponding to
the barrier configuration (beam length, type and quantity of accessories
installed) given in Table 4 or Table 5 on page 25 (for example, choose
the default
04 for a beam L of 5 metres with lights and foot).
To complete configuration, it is necessary to exit the BASIC
programming menu by pressing “F” until parameter
St is reached or
by pressing “F” and “-”
This operation changes the value of the parameters
So and SC in BASIC programming and FO, FC, oc in
ADVANCED programming, setting them on the default
values as shown in the tables in paragraph 6.3.
Setting a set of pre-defi ned parameters that does not
correspond to the actual confi guration of the barrier could
cause irreversible damage to the automated system, in
particular if the default corresponds to a beam length
shorter than the actual one.
00 Beam closed
05 Opening
01 Beam open /
04 Pause
06 Closing