20
ENGLISH
Display Fucntion
Default
0
Default
1
Default
2
Default
3
Default
4
Default
5
o2
OUT 2:
Used for setting the OUT1 output (open collector N.O.):
00 = Always active
01 = FAIL-SAFE
02 = INDICATOR LIGHT (off when closed, lighted during
opening and open/pause, flashes during closing)
03 = COURTESY LIGHT (see next parameter)
04 = ALARM on BATTERY operation
05 = gate OPEN or in PAUSE
06 = gate CLOSED
07 = gate MOVING
08 = gate in EMERGENCY status
09 = gate OPENING
1 0 = gate CLOSING
1 1 = ELECTRIC LOCK command before CLOSURE (you
have to interface with relay 24V – 100mA)
1 2 = safety device ACTIVE
1 3 =
‘TRAFFIC LIGHTS’ function (activates during OPENING
and when gate OPEN)
1 4 = timed output; it can be activated from the second
radio channel OMNIDEC (see next parameter)
1 5 = this output can be activated from the second
radio channel OMNIDEC (step-by-step function
)
1 6 = electric lock before an OPENING (you have to
interface with relay 24V – 100mA)
Other more detailed programming pos-
sibilities are feasible by programming with
a PC (see dedicated instructions).
02 02 02 02 02 02
t2
TIMING OUT 2 (only visible if at the previous step
o 2
the item 0 3 -1 1 -1 4 -1 6 was selected):
Adjusts the timing of output OUT 2 if a timed function from
1 to 99 minutes in 1-minute step was selected for the
functions 0 3 -1 4 and from 1 to 99 seconds in 1-second
step for the functions 1 1 -1 6 .
02 02 02 02 02 02
X
RESET and X-COM RADIO MODULE ACQUISITION:
The X-COM module is used for radio communication between
board and PC. Before enabling a communication, the X-COM
module must be configured.
If no is displayed when entering this menu, this means that
the X-COM module has not yet been configured or fitted. To
start the configuration procedure, fit the module in the M1A-
XCOM connector on the board and hold down push-button +
for 5 sec. Y will appear on the display and the flashing light will
operate. The configuration procedure must then be terminated
from the PC. If Y is shown when you enter this menu, this means
that the X-COM module has been configured and is ready to
communicate. The X-COM module can be reset by holding
down the – key for 5 seconds.
Y = X-COM module enabled to function.
no = no X-COM module fitted or configured.
no no no no no no