EasyManua.ls Logo

F&F LE-03MB - How to Use Broadcast Command to Set Baud Rate; How to Set Primary Address; How to Set the Address of a Slave to 01; How to Use Broadcast Command to Set Primary Address to 01

F&F LE-03MB
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LE-03MB - User manual
27
9.2.2. How to use broadcast command to set baud rate
Format:
Start
L field
L field
Start
C field
A field
CI field
Check sum
Stop
68H
03
03
68H
53/73
FF
B8-BD
CS
16
Slave to Master: No answer
B8-------300
B9-------600
BA-------1200
BB-------2400
BC-------4800
BD-------9600
Example:
Change all the meter's baud rate to 2400 bps.
Master to Slave: 68 03 03 68 53 FF BB 0D 16
Slave to Master: No answer
9.3. How to set primary address
9.3.1. How to set the address of a Slave to 01
Format:
Start
L field
L field
Start
C field
A field
CI field
DIF
VIF
Address
data
Check
sum
Stop
68H
06
06
68H
53/73
FE
51
01
7A
XX
CS
16
Example:
Master to Slave: 68 06 06 68 53 FE 51 01 7A 01 1E 16
Slave to Master: E5
9.3.2. How to use broadcast command to set primary address to 01
Format:
Start
L field
L field
Start
C field
A field
CI field
DIF
VIF
Address
data
Check
sum
Stop
68H
06
06
68H
53/73
FF
51
01
7A
XX
CS
16
Example:
Master to Slave: 68 06 06 68 53 FF 51 01 7A 01 1F 16
Slave: No answer

Table of Contents