EasyManua.ls Logo

F&F LE-03MB - How to Change Address from 01 to 02; How to Set Primary Address to 01 by Using Secondary Address; Set the Complete Identification of the Slave

F&F LE-03MB
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LE-03MB - User manual
28
9.3.3. How to change address from 01 to 02
Format:
Start
L field
L field
Start
C field
A field
CI field
DIF
VIF
Address
data
Check
sum
Stop
68H
06
06
68H
53/73
XX
51
01
7A
YY
CS
16
XX - current primary address
YY - new primary address
Master to Slave: 68 06 06 68 73 01 51 01 7A 02 42 16
Slave to Master: E5
9.3.4. How to set primary address to 01 by using secondary address
Example: secondary address: 12345678
Step 1
Initialize the Slave
Master to Slave: 10 40 FF 3F 16
Slave to Master: No answer
Step 2
Check the secondary address. After receiving the command, the Slave will check if the secondary address in the
command is same with its secondary address or not.
Master to Slave: 68 0B 0B 68 73 FD 52 78 56 34 12 FF FF FF FF D2 16
FD --- the primary address used when you use secondary address to read data.
78 56 34 12 - the meter’s secondary address is 12 34 56 78
Master to Slave: E5 (success)
Step 3
Change the primary address to 01
Master to Slave: 68 06 06 68 73 FD 51 01 7A 01 3D
01 --- new primary address
Slave to Master: E5
9.4. Set the complete identification of the Slave
(ID=12345678, Man=4024h (PAD), Gen=1, Med=02 (energy)
Start
L field
L field
Start
C field
A field
CI field
DIF
VIF
68H
0D
0D
68H
53/73
addr
51
07
79
Identification
No
Manufacturer
ID
Generation
Medium
Check
sum
Stop
4 byte
2 byte
1 byte
1 byte
CS
16
For example: (Meter address is 01)
Master to Slave: 68 0D 0D 68 53 01 51 07 79 78 56 34 12 24 40 01 02 A0 16
Slave to Master: E5