9.14. Set up the output mode of pulse 1
Example: (Meter address is 01)
Master to Slave: 68 04 04 68 11 01 11 01 24 16
Slave to Master: E5
The red-lighted 01 represents the output mode of Pulse1:
01: Import active energy
02: Import + export active energy
04: Export active energy (default)
05: Import reactive energy
06: Import + export reactive energy
08: Export reactive energy
9.15. Read the constant of pulse 1
Example: (Meter address is 01)
Master to Slave: 68 03 03 68 11 01 12 24 16
Slave to Master: 68 04 04 68 11 01 10 00 22 16
The red-lighted 00 represents the constant of pulse 1:
00: 0.0025 kwh (kvarh)/pulse (default)
01: 0.01 kWh (kvarh)/pulse
02: 0.1 kWh (kvarh)/pulse
03: 1 kWh (kvarh)/pulse
04: 10 kWh (kvarh)/pulse
05: 100 kWh (kvarh)/pulse
9.16. Set up the constant of pulse 1
Example: (Meter address is 01)
Master to Slave: 68 04 04 68 11 01 13 00 25 16
Slave to Master: E5