9.11. Read the measurement mode
Example: (Meter address is 01)
Master to Slave: 68 03 03 68 11 01 09 1B 16
Slave to Master: 68 04 04 68 11 01 09 01 1C 16
The red-lighted 01 represents the measurement mode:
01: means active energy
02: means active energy + reactive energy
03: means active energy - reactive energy
9.12. Set up the measurement mode
Example: (Meter address is 01)
Master to Slave: 68 04 04 68 11 01 0A 01 1C 16
Slave to Master: E5
The red-lighted 01 represents the measurement mode:
01: means active energy
02: means active energy + reactive energy
03: means active energy - reactive energy
9.13. Read the output mode of pulse 1
Example: (Meter address is 01)
Master to Slave: 68 03 03 68 11 01 10 22 16
Slave to Master: 68 04 04 68 11 01 10 01 23 16
The red-lighted 01 represents the output mode of pulse 1:
01: Import active energy
02: Import + export active energy
04: Export active energy (default)
05: Import reactive energy
06: Import + export reactive energy
08: Export reactive energy