EasyManua.ls Logo

FBD 772 - Diagnostic Fault Codes

FBD 772
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Error #140: Low regulated CO2 PSI
The regulated CO2 pressure dropped below 50 PSI.
1 Ensure the CO2 supply is not low.
2 Check the “carbonation” regulator on the header tray and ensure it is set to 60 PSI.
Error #150: High regulated CO2 PSI
The regulated CO2 pressure is above below 70 PSI.
1 Check the “carbonation” regulator on the header tray and ensure it is set to 60 PSI.
Error #160: Low Line Voltage
The voltage supply is below 200 volts
1 Install a boost transformer. Even if the voltage is slightly above 200 V a boost transformer may
be needed as fluctuations in power during the day or during unit operation may cause it to drop
below 200 volts and shut down the unit.
Error #170: High Line Voltage
The voltage supply is above 254 volts
1 Install a buck transformer.
Error #180: LPSI transducer
The low side refrigeration pressure is not reading correctly.
1 Ensure the pressure transducer is plugged in.
2 Replace the transducer if faulty.
Error #190: HPSI transducer
The high side refrigeration pressure is not reading correctly.
1 Ensure the pressure transducer is plugged in.
2 Replace the transducer if faulty.
Error #200: Return Temperature Sensor
The refrigeration return (suction) temperature sensor is not reading correctly.
1 Ensure the temperature sensor is plugged in.
2 Replace the sensor if faulty.
Error #210: Refrigeration Malfunction
The refrigeration pressures were not in the correct range.
1 Run the fill diagnostic sequence to determine the reason for the failure.
Diagnostic Fault Codes
The following codes are faults that can be displayed after running a diagnostic sequence.
Error #500: Fan not turning on
1 Remove control board and check for a blown fan fuse (F1 and F2). If a fuse is blown then a
fan or capacitor malfunction may be possible.
2 If fuses are OK, reinstall control board.
3 Disconnect wiring harnesses at fan capacitor.
4 Manually turn fan on and check for line voltage (230V) between the connectors removed from
the capacitor. If no voltage is present then replace control board.
5 If correct voltage is present then substitute a “known to be good” capacitor and try to operate
fan again.
6 If fan fails to start with good capacitor then replace both fan and capacitor.

Other manuals for FBD 772

Related product manuals