EasyManua.ls Logo

FBD FBD564 - Page 29

FBD FBD564
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
(Item 13.3 continued from previous page.)
D. Syrup or Water Pump failure. D. Check all pumps and replace, if
necessary.
E. CO
2 or water can’t keep up E. Reroute water or CO2 lines to
with unit demand. maximize supply pressure. Install
Water Booster if necessary.
F. Excessive pressure drops F. Observe “Syrup Press” readouts
in syrup lines. as chamber fills to verify. Increase
line diameter or relocate syrup
source closer to unit. Syrup
pressures may only be raised (by
increasing pump CO2 pressure)
if separate regulators are installed
for unit and syrup pumps. Never
exceed pump manufacturer’s
recommended maximum CO2 inlet
pressure (see Section 12.4).
G. Transducer problem (H2O, G. Check pressure readouts (H2O,
CO2 or Syrup). CO2 and Syrup) for 70-72 psig. If
not within 2 psi, adjust regulator
and/or check transducer. Replace
transducer, if necessary.
H. Lower Board problem H. Check Lower Power Board for +5,
+15, and –15 indicator lights. If
green lights are not energized,
replace board, if necessary.
I. Upper Board Problem I. Circuits within Main Control (Upper)
Board electronics read transducer
pressures. Replace Main Control
(Upper) Board, if necessary
13.4 Product does not flow A. Faulty CO2 check valve. A. Inspect CO2 check valve. Clean or
freely or does not flow replace.
at all from dispensing B. CO2 solenoid valve won’t B. In “Manual On/Off, energize
valve. open. solenoid and check for 24VAC at
coil. Clean or replace solenoid, if
necessary.
C. Solution solenoid valve C. In “Manual On/Off”, energize
won’t open. solenoid and check for 24VAC at
coil. Clean or replace solenoid, if
necessary.
D. Ice particles in dispensing D. Run defrost cycle. If necessary,
valve. open and close dispensing valve
several times or run warm water
over valve.
E. Product in cylinder is frozen E. 1. Check water/syrup flow
too hard or solid. rates and brix. Adjust, if
necessary (see Section 6.2).
2. Check Level Control setting.
Adjust if necessary (see
Section 10).
3. Check Thaw/Freeze settings.
Adjust if necessary (see
Section 11).
4. Defrost chamber. Assure
chamber is filled to 90%, then
press “Run”.
13.5 Product leaking from A. Beater drive seal is worn or A. Replace with new seal.
rear of cold pack. damaged.
B. Beater drive coupling is worn. B. Replace coupling.
C. Seal is not positioned C. From inside chamber, reseat seal,
correctly. making sure it is flush with back of
chamber.
TROUBLE CAUSE REMEDY

Table of Contents

Related product manuals