Fitting and installing the pneumatic components
Mount the SPC-10 horizontally or vertically on a level surface
with the aid of the support brackets supplied. You will require at
least 3 screws (M4) here.
Compressed air / service unit
• 5 to 7 bar, dried, non-lubricated 5
µ
m filter element
• Max. deviation in compressed air at the MPYE-5-... +/- 1 bar
• Sufficient standard flow (reference value: twice the standard
flow of the valve)
• Microfilter if slight oil mist cannot be avoided.
Proportional directional control valve (type MPYE-5-...)
• This should be fitted and connected up symmetrically to the
centre of the cylinder. If fitted to moving parts, the
MPYE-5-... should be mounted at right angles to the
direction of movement.
• Fit silencers with large rated flow (e.g. U-1/8), maximum
length of tubing 1 m.
Compressed air tubing and screw connectors
• Lay the tubing from the valve to the cylinder symmetrically.
Tubing length = cylinder length.
• Dimensions corresponding to rated size of the service unit,
the proportional directional control valve and the cylinder.
• If angled connectors cannot be avoided, use plug
connectors from the Quick Star series.
• Do not use any restrictors in the supply tubing.