9. APPENDIX C. REFERENCE
Specications
Compliance with UL Regulations
For UL compliance, the following instructions must be met
when operating the ProtoNode.
The units shall be powered by listed LPS or Class
2 power supply suited to the expected operating
temperature range.
The interconnecting power connector and power
cable shall:
Comply with local electrical code.
Be suited to the expected operating temperature
range.
Meet the current and voltage rating for the
ProtoNode/Net.
Furthermore, the interconnecting power cable shall:
Be of length not exceeding 3.05 m (118.3”).
Be constructed of materials rated VW-1 or FT-1
or better.
If the unit is to be installed in an operating environment
with a temperature above 65 °C, it should be installed
in a Restricted Access Area requiring a key or a
special tool to gain access.
This device must not be connected to a LAN segment
with outdoor wiring.
Specication ProtoNode RER ProtoNode LER
Electrical
Connections
One 6-pin Phoenix connector,
one RS-485 +/- ground port,
power +/- frame ground port,
One 3-pin RS-485 Phoenix connector,
one RS-485 +/- ground port,
One Ethernet-10/100 Ethernet port
One 6-pin Phoenix connector,
one RS-485 +/- ground port,
power +/- frame ground port,
One Ethernet 10/100 BaseT port,
One FTT-10 LonWorks port
Approvals
Pending CE (EN55022; EN55024; EN60950), UL916, Pending FCC Class A Part 15, DNP3
Conformance Tested, OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked LonMark Certied
Power
Requirements
Multi-mode power adapter: 9-30VDC or 12 - 24VAC 2.5 W
Physical
Dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Weight 0.2 kg (0.4 lbs)
Operating
Temperature
-40°C to 75°C (-40°F to 167°F)
Surge
Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity 5 - 90% RH (non-condensing)