FVA-IP Camera Installation and Operation Manual
Revision Date: June, 2019 P/N 06-523 (Rev. 5) 23
Thefinalsubmenufeature is the camerasSensitivitySettings,Figure19.Allthreealgorithmsarebydefaultsetto
mediumandthedynamicfunctionissettooff.ThesystemisFMapprovedforasensitivitysettingofmediumforboth
flameandsmoke.
NOTE:TheOffsitealgorithmisnotanFMapproveddetectionmethod.
Thefire,smokeandoffsite(reflectedfirelight)algorithmscanbesettolowmediumorhigh.Thesmokealsohasan
ultrasensitivitysettingusedforverycleanandstableenvironments.Thedynamicsettingisusedinapplicationsthat
havelightfluctuationsdoto windows,largedoors,orprocessesthatmakethebackgroundimageunstableandmay
causenuisancealarms.Thesystemisforindoorapplicationsonly.
Fig19–Sensitivitysettings