EasyManua.ls Logo

Fire-Lite 411UD - Transmittal Priorities; Event Priority Order

Fire-Lite 411UD
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
411UD Document #50759 Rev. E 12/09/2008 P/N 50759:E 43
Central Station Communications
4.0.1 Transmittal Priorities
The digital communicator transmits highest priority events first. Events in terms of priority are listed below in
descending order:
1. Fire Alarm (highest priority level)
2. Fire Supervisory
3. System Troubles
Host Panel Trouble (active input programmed for trouble)
AC Fail (after delay)
Channel/Input faults
Telephone line fault
Communication trouble
System Off Normal
4. Restoral Reports
Fire Alarm
Fire Supervisory
Host Panel Trouble
AC
Channel/Input fault
Telephone line
Communication
System Off Normal
5. System Test
6. Upload/Download events (lowest priority)
Red LEDs are provided on the digital communicator circuit board to identify which telephone line is active.

Table of Contents