411UD Document #50759 Rev. E 12/09/2008 P/N 50759:E
A.2 Digital Communicator Options Program Sheet (Factory Defaults)
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
20
Primary Central Station Communication Format: 'E' for Ademco Contact ID Format.
21
22
23
24
Primary Central Station Account Code.
25
26
27
28
Primary Central Station 24-hour Test Time. '0000' = 12:00 midnight.
29
Primary Number Test Time Interval. '0' for 24 hours.
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
50
Secondary Central Station Communication Format. 'E' for Ademco Contact ID Format.
51
52
53
54
Secondary Central Station Account Code.
55
56
57
58
Secondary Central Station 24-hour Test Time: '0000' = 12:00 midnight.
59
Secondary Number Test Time Interval. '0' for 24 hours.
60
AC Loss Reporting Delay. '2' for 2 hour delay.
61
Backup Reporting. '0' to report to Secondary Central Station phone number as backup only.
62
Future Use.
63
Future Use.
64
Communicator Enable/Disable. '0' disables communication to Central Station.
65
Input Channel 1 Function Selection. '0' for fire alarm.
66
Input Channel 2 Function Selection. '1' for host control panel trouble.
67
Input Channel 3 Function Selection. '2' for fire supervisory.
68
Input Channel 4 Function Selection. '4' for AC loss.
69
70
71
Input Channel 1 Delay Timer. '000' for no delay. Does not delay fire functions.
72
73
74
Input Channel 2 Delay Timer. '000' for no delay. Does not delay fire functions.
75
76
77
Input Channel 3 Delay Timer. '000' for no delay. Does not delay fire functions.
78
79
80
Input Channel 4 Delay Timer. '000' for no delay. Does not delay fire functions.
81
Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
82
Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.
F F F F F F F F F F F F F F F F F F F F
0 0 0 0
E
0
0 0 0 0
0 0 0 0
0 0 0 0
E
0
2
0
1
0
0
0
1
2
4
0 0 0
0 0 0
0 0 0
0 0 0
0
0