Table 3: UI buttons
Button icon Button description Button functionality Button availability
Lamp test See Using the lamp test
button
In access level 1, 2, and
3
Function See Using the function
button
In access level 1, 2 and
3
Silence/resound/
evacuation
See Using the silence/
resound/evacuation
button
In access level 2 and 3
Right navigation See Using the right
navigation button
In access level 2 and 3
Left navigation See Using the left
navigation button
In access level 2 and 3
Using the enable/disable button
Press the Enable/Disable button in the following events:
• To enable or disable the sounder and zones.
• To turn on and off the delay to output on individual zones.
Using the reset button
To reset the state of the panel, press the Reset button. The following events then occur:
• The panel turns off the detectors for 2 seconds. The alarm clears from the panel after reset.
If an alarm condition remains, the alarm indications and sounder restart.
The power to auxiliary outputs turns off for 5 seconds.
The reset output then activates for 5 seconds and turns off. See Resetting the fire alarm.
Using the buzzer silence button
• To silence the buzzer in either a fire or fault event, press the Buzzer Silence button.
Using the lamp test button
• When you press the Lamp Test button for 5 seconds, all the LEDs on the panel and the buzzer
turn on for 10 seconds, then turn off again.
Using the function button
Press the Function button in the following events:
• To enter programming mode in access level 2 and 3.
5FireClass Essential Panels User Manual