Figure 12.3: Zones programming window for the FC506 panel
Outputs programming
The Panel outputs option allows you to access the output
parameters. The relevant programming appears as per the
description in Figure 13.
SC1, SC2 outputs
These are supervised, silenceable, bypassable (disabled)
Alarm outputs. For an Active output, pull up to 27.6V on
the positive terminal; pull down to 0V on the negative
terminal. When you click on an output, the relevant
programming window appears.
General section
Enabled: A tick indicates an enabled output.
Label: This is for the editable Output-label. The
system uses the label as the Output identifier.
Zones
In the Zones section, it is possible to trigger each output by
up to four of the available software zones (32 for the
FC501, 128 for FC503 and 256 for the FC506 fire panel).
Trigger points
In the Trigger points section, it is possible to trigger each
output by three input points. For each point, you need to
indicate the device address; in the case of FC506, you
need to indicate both the loop number and device address.
Options
In the Options section, you can select the conditions that
will activate the outputs. For example, if the Zone warning
option is enabled, the control panel activates the output
when one of its associated points goes into Warning
status.
Warning zone, Fault zone, Delay to alarm zone,
Alarm zone, Double knock (see Zones
programming), Walk test zone
Point warning, Point fault, Point delay to alarm,
Point alarm
Panel warning, Panel fault, Panel Delay to Alarm,
Panel alarm, Network RS485 fault
Set as SC1. If this option is enabled, the output
behaves as SC1.