22
Note: In the description of events, the devices are
described as belonging to a loop. In the case of open
loops, you cannot distinguish between the left and right
side. However, the loop concept is not meaningful by
definition, and localization occurs via zones, the same way
as conventional panels.
Note: For the FC503 panel, if devices are addressed by
the service tool, there is an option to set the devices in six
zones that correspond to the 6 spurs. Assign the correct
zone to each device using the PC console or a control
panel LCD.
Note: If you do not address the devices, the mapping
procedure will occur to locate each device and assign the
proper zone to it.
Day or Night mode: Select the operation mode,
Day mode or Night mode, or select Automatic to
set the time (hour and minutes) of transition from
one mode to another.
Disable screen saver: This allows the user to
enable or disable the screen saver on the main
page of the control panel LCD. You can program
the screen saver from the control panel user
interface or via the FireClass FC500
(FC501_FC503_FC506) console. If you have an
enabled screen saver, it appears on the LCD. If
the screen saver is disabled, it does not appear.
This feature is unavailable for repeaters.
Power supply: Select the system power supply,
BAQ140T24.
Disabling: Disable SC1. This allows you to
disable the SC1 output (enabled by default). This
is a programmable output. Activation occurs every
time the control panel goes into Alarm status.
Reactivation of new alarm: You can select the
following options:
No Reactivation: Outputs here are not
reactivated once silenced
Alarm on other zone: Outputs here reactivate
once a new zone goes into Alarm status.
Users
In the Users section, you can change the installer and the
user codes. Each code must have five digits and they can
include digits 0-9.
The installer code allows you to manage the three
access levels: Level 1 (View), Level 2 (User) and
Level 3 (Installer).
The default installer code is 00000:
One click only means the password is present.
A second click means the password is enabled.
The user code allows you to manage two access
levels of the control panel: Level 1 (View), Level 2
(User).
The default user code is 11111:
Once click only means the password is present.
A second click means the password is enabled.
Lock installers password: If you select this
option, it is not possible to perform the procedure
to reset the installer password after removing
Jumper J5.
Communicators
In the Communicators section, you can enable the PSTN
functionality and the FC500IP module.
PTSN
In the PSTN section:
One click only means the PSTN is present, but not
enabled.
A double click means the PSTN is enabled.
When you enable PSTN, you can also select whether to
enable both events, alarms and faults (and one of two).