28
Note: By selecting Override, it is possible to adjust the
panel ID for export and import. If the option Any panel
[XXXX] is implemented, you can utilise this configuration in
any panel (for example, to load the same voice messages
in several panels).
Note: In the printer driver, set the Page resizing option to
None.
Note: You can move the database from one system to
another. The console searches for the wire database on
start up. If you cannot access a moved database, close the
software and restart.
Battery calculation
The Battery calculation window allows you to see the
following (see Figure 16):
The FC501 and FC503 loads: Loop 1, Loop 2,
Loop 3 device loads.
The FC506 loads: Loop 1, Loop 2, Loop 3, Loop 4,
Loop 5, Loop 6 device loads in the condition of
Normal load and Alarm loads (percentage of
devices in Alarm status), when the Mains fails.
Below this window, in the option Others load, you
can insert Loads on auxiliary terminals if required.
Automatically, the Total load, the Battery needed
and the Battery recharge time appears. Set the
Standby hours, Alarm minutes values and the
calculation will occur.
Battery calculation parameters
Stand-by hours (from 1 to 144h)
Alarm minutes (from 1 to 240m)
Battery type
This is the battery (Ah) arising from calculation.
Battery calculation constraints
Lock standby hours
Lock battery type
Lock standby hours
Battery type value (Ah) will be calculated, fixed Standby
hours, Alarm minutes.
Lock battery type
Standby hours value will be calculated, fixed Battery type
(Ah), Alarm minutes.
Note: The software calculation is a rough calculation and
cannot substitute the installer or qualified person’s
calculation.
Figure 15: Page to print the zones label