Speed: If this Auto option is disabled, set the
speed value as appropriate, 10 Mbps or 100
Mbps.
Duplex: If this auto option is disabled, set the
Data exchange, duplex mode as appropriate,
either half or full.
Read-only options
You cannot modify the values in this section. They display
information relating to the connected IP module.
MAC address: Displays the MAC address of the
IP module; the MAC address is a unique
identification number assigned to every IP device
in the world.
Firmware version: Displays the version of the
program running on the IP module.
Boot version: Displays the boot version.
Current IP address: Displays the IP address
assigned to the IP module.
General options
Use this section to select the general options for the IP
module.
Encryption key: If this has been programmed, the
IP module uses this key to encode and decode the
packets exchanged with the computer. The
encryption key may include between 1 to 32
hexadecimal characters (numbers 1 to 9 and
letters A to F). To disable encryption, enter 0. If
the encryption key does not correspond to that of
the IP module, communication between the
computer and the IP module is not permitted. The
default setting is 0 (encryption key not enabled).
Board port: You should use this port to
communicate with the IP module. The default
setting is 3064.
Pass through port: You should use this port to
communicate with the control unit. The default
setting is 3062.
Board code: You should apply this code when the
FireClass FC500 (FC501_FC503_FC506)
Console is used to program the IP module, either
remotely or locally. The code should consist of
four hexadecimal figures. The default setting is
5555.
Idle connection timeout: Enter the maximum
time period during which no data is transmitted,
before the connection terminates. The default
setting is 20 seconds.
Address book
Account code: The central station uses this account
number to distinguish between transmitters. There is one
account number programmable for the FC500IP. The
default value is 0000FFFFFF.
Note: Account codes 0000FFFFFF, FFFFFFFFFF and
0000000000 are not valid accounts.
Supervision: To enable Supervision mode, tick this
option.
Main
IP Address: This is a static IP address for the
receiver. Program the IP address of the central
station receiver. If an IP receiver is not connected,
program the 0.0.0.0 address. The default value is
000.000.000.000.
Local port and remote port: These values show
the ports that communicate with the receiver. The
same receiver supplies these values. The default
values are 3060 (local port) and 3061 (remote
port).
Backup
Receiver IP: This is the static IP address for the
second receiver. Program the IP address of the
second receiver. The default value is
000.000.000.000.
Note: The receiver is used for backup only; this is not
checked.
Local port and remote port: These values
represent the ports used for communication with
the backup receiver. Default values are 3065
(local port) and 3066 (remote port).
Third
Receiver IP: This is the IP address assigned to
the domotics system receiver. The receiver itself
supplies the IP address. The default value is
40000.
Local port and remote port: These values
represent the ports used when communicating
with the domotics system receiver. The receiver
supplies the values. The default value is 40001.
The receiver is used for the domestic system only;
Advanced
LED Trouble mask/ Output Trouble mask
You can use this section to enable or disable signals from
the OC output and the indicator light, for certain events
recognised by the IP module: Network absent. A tick
indicates that the corresponding event is detected. By
default, the LAN undetected event indication is enabled.
Output polarity
Use this section to set the operating mode of the OC
output on the IP module.
Open on trouble: At default, the outlet suspends
when a breakdown occurs.