BURNERPRO SYSTEM SPECIFICATION
Supply Voltage:
BP110 110 VAC (+20%, -15%) 50/60 Hz, single phase
BP230 230 VAC (+10%, -15%) 50/60 Hz, single phase
Power Consumption:
7 VA
Temperature Rating:
Operating: -40°C to +60°C (-40°F to 140°F)
Storage: -50°C to +85°C (-58°F to 185°F)
Flame Amplifier Rating:
UV: Terminals 22 & 23, 300VDC 3mA(max)
FR: Terminals 24 & Earth, 330VAC (max), 3uA min/10uA max flame current
Protection Category:
IP40 standard version
Control Dimensions:
With wiring base (60-2944-1); 4.15” L x 4.15" W x 5.0" H (105mm x 105mm x 127mm)
Shipping Weight:
Approx. 2.5 lbs. (1.13kg)
OPERATING TEMPERATURE LIMITS
Relative Humidity:
90% R.H. (Non-Condensing)
LOAD RATINGS:
Maximum connected load must not exceed 2000VA.
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar devices
whose inrush current is approximately the same as their running current.
CONTROL MAXIMUM MINIMUM
BP110, BP230
140°F 60°C -40°F -40°C
UV90L-1
194°F 90°C -40°F -40°C
UV1AL-3, -6
200°F 94°C -40°F -40°C
UV5-1
140°F 60°C -4°F -20°C
Terminal Typical Load Maximum Rating
@120V-50/60 Hz
Maximum Rating
@230V-50/60 Hz
Alternate Rating
6-7 Burner/Blower
Motor
2 F.L.A. *
8 L.R.A.
2 F.L.A. *
8 L.R.A.
240 VA Pilot Duty
(Motor Starter Coil)
9-10-11-20 Modulator 240 VA Pilot Duty
16-17-18-19 Fuel/Igniton 240 VA Pilot Duty
3 Alarm 125 VA Pilot Duty
* F.L.A. = full load amps; L.R.A = locked rotor amps