33
®
40207 206 1 AUTO Release to modulation drive state:
0x00: OFF
0x01: ON
40208 207 1 Recycle Limit Recycle limit terminal state:
0x00: OFF
0x01: ON
40209 208 1 POC Proof of closure terminal state:
0x00: OFF
0x01: ON
40210 209 1 CAST Combustion air switch test terminal state:
0x00: OFF
0x01: ON
40211 210 1 CAP Combustion air prove terminal state:
0x00: OFF
0x01: ON
40212 211 1 Actuator feedback Actuator feedback terminal state:
0x00: OFF
0x01: ON
40213 212 1 Valve Proving States Valve proving test states:
0x00: Test not started
0x01: Test started
0x02: Evacuate test space
0x03: Test Time 1 phase
0x04: Test time 1 complete
0x05: Pressurize test space
0x06: Test time 2 phase
0x07: Test time 2 complete
0x08: Valve proving complete
0x09: Valve proving complete
40214 213 1 Valve prove test counter Countdown timer for valve proving in sec
40215 214 1 Actuator feedback
counter
Actuator feedback waiting timer
40216 215 1 CAST timer Combustion air switch test waiting timer
40217 216 1 CAP timer Combustion air prove waiting timer
40218 217 1 POC counter Proof of closure waiting timer
40219 218 1 Pre-purge counter Pre-purge countdown timer
40220 219 1 Post-purge counter Post-purge countdown timer
40221 220 1 Check mode timer Check mode timer
40222 221 1 Remote Reset attempts Shows the number of remote reset applied
by the user in the alloted window [15mins]
40223 222 1 Reset inhibit timer Countdown timer to restore remote reset
operation
40224 223 1 Burner minutes Burner ON minutes
40225 224 1 Burner seconds Burner ON seconds
40226 225 1 System minutes System ON minutes
40227 226 1 System seconds System ON seconds
40228 227 1 Operating frequency
(MCU 1)
Line voltage frequency:
0x00: 50Hz
0x00: 60hz