34
40229 228 1 Operating frequency
(MCU 2)
Line voltage frequency:
0x00: 50Hz
0x00: 60hz
40230 229 1 Terminal 15 (VPS) Status of terminal 15
0x00: Inactive
0x01: Active
40231 230 1 Burner cycle count Number of burner cycles completed
40232 231 1 Cycle hold timer countdown to show the expiration of inter-
cycle delay
40233 232 1 Flame permissible timer Countdown to show allowable flame
afterburn
40234 233 1 Flame sensor Flame sensor input identified during the
burner sequence:
0x01: UV
0x02: FR
40235 234 1 Flame strength Flame strength based raw sensor input
40236 238 1 Reset source Reset source:
0x00: No reset
0x01: Local reset (button)
0x02: Remote terminal reset
0x03: Modbus reset
40240 239 1 Lockout count Total system lockout count
40241 240 4 Lockout history 1 (most
recent)
BurnerPRO stores the last 10 lockout
information. Each lockout history is stored
using 4 words:
1st word: Lockout reason code
2nd word: Burner state at time of lockout
3rd word: Burner minutes
4th word: Burner cycles
40245
244 4 Lockout history 2
40249
248 4 Lockout history 3
40253
252 4 Lockout history 4
40257
256 4 Lockout history 5
40261
260 4 Lockout history 6
40265
264 4 Lockout history 7
40269
268 4 Lockout history 8
40273
272 4 Lockout history 9
40277
276 4 Lockout history 10