EasyManua.ls Logo

Fisher DPR900 - Page 32

Fisher DPR900
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-72 rnsfa//afion
2.11
Ground Loops and Common Mode
Voltage
Ground loops occur when either the return wire or the sensor is
grounded at the process line and Jumper 5 on the mounting cassette
is intact. To correct this situation, the input should be connected as a
differential input (Jumper 5 cut). The input then floats with respect to
supply ground. The maximum common mode voltage (CMV) the
controller should receive when wired in this manner is -5 to +I7 volts
taken from the input negative pole to supply ground. If these limits are
expected to be exceeded, an isolation amplifier must be used.
For each of the points 1 thru 4 in the following
example, the table lists the maximum potentials
and grounding possibilities.
4 - 20mA
SeWDr
I
CMV referred
to this point
UM6.1:DPF?900:9147
Change 2 -July 1992

Related product manuals