5-32
Configuration
5.7.7
I-J
LSP
Upon return to the auto mode, the LSP value will be the same as the
PV signal. Use FCODE 140 to select tracking of PV in the manual
mode.
Function Function FCODE FCODE
Option Option No Default No Default Selected Selected
Value Value V&X V&X
Setpoint Setpoint
140 140 Disabled Disabled 1 1 1 1
Tracking Tracking Enabled, tracks RSPIESP Enabled, tracks RSPIESP 2 2
(LW (LW
Enabled, tracks PV in Manual Enabled, tracks PV in Manual 3 3
The local setpoint tracks the PV in manual ONLY
when the manual command comes from the front
panel or via computer. If manual mode is lorced
via a discrete input, Option 3 does not take effect.
Setpoint Limits
The user may configure operational limits to the setpoint value, to
prevent the controller from using a setpoint value outside such
configured limits. The limits apply to both local and remote setpoint
values.
Function FCODE
Option No Default Selected
Value
Value
Setpoint
106 Disabled
0 0
Limits Enabled 1
Function
Parameters
FCODE Range Unit Increment Default Selected
ValW V&K2
Setpoint Low limit
9 MEJS.
a”Y
1 digit Min
Limits High limit 10 Range
a”Y
1 digit Max
tJM6.1:DPR900:9102