Configuration
5-27
Remote Setpoint (RSP)
The DPRSOO can be configured to receive an externally generated
signal and use it as a remote setpoint (RSP). The controller receives
the RSP value via analog input Al2 and uses this, or the extra internal
setpoint, as the setpoint value when the user pressed the R button.
The user may condition the incoming remote signal using the
following functions:
Function Parameters FCODE Range
Unit
Increment Default Selected
Vallle Vallle
Ratio Gain
1 o-9.99 0.01 1
(A1.3
J
Function
Parameters
FCODE Range Unit Increment Default Selected
V&e V&e
Bias Zero level offset
2 + Meas.
=“Y
1 digit 0
W)
Range
Function Parameters FCODE Range
Unit Increment Default Selected
Value
ValUe
Filter Al2 Time constant 16 o-9999 s
IS
0
Function FCODE
Option NO Default Selected
Value
V&X
Signal
120 4-ZOmA, 1%5V 1 1
Range O-ZOmA, 0-5V 2
VW
4-ZOmA, l-5V, Square root 3
C-ZOmA, C-5V. Square root
4
An arithmetic expression (or calculation), can be selected using
FCODE 108. The result is used as the RSP input. The values of
Ration and Bias are determined by FCODE 1 and 2.
I I
Al2 -
FCODE 16 FCODE 120
Filter Square Root
FCODE 106
Arithmetic
- RSP
A,3 _ FCODE 17
FCODE 121
Filter
- Square Root
DPR900~-034
May 1991
UM6. I:DPR900:9102