Fisher DPR900 - Setpoint Handling and Source Selection

Fisher DPR900
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function FCODE Option No Default Selected
Vahe Value
output
114 Disabled 0 0
Selector Process value
1
A02
Active setpoint
2
Local setpoint
3
Calculated Remote setpoint 4
Internal output signal 5
Set FCODE 124 to select the A02 output signal range:
Function FCODE Option No Default Selected
Vaille Value
Signal 124 4-20mA output signal
1
Range
0-20mA output signal 2 2
A02
If A02 has been configured using FCODE 114,
Option 1-5 and there is no circuit path between
pins 11 and 12, the controller self-test reports an
Error (E 103). The self-test is looking for the
minimum 4 mA signal based on the configuration
Either configure to FCODE 124, Option 2 or
complete the output circuit between Terminal 11
and 12 with a jumper wire.
The A02 output signal represents the actual
bargraph value (O-100%). If the setpoint limiting
function (FCODE 106) is enabled, the output
signal is resealed to represent O-l 00% of the
limited output span, not necessarily the full SP or
PV potential.
5.7 Setpoint Handling
This section describes the five possible sources for the controller
setpoint.
May 1991 uM6.1:DPR900:9102