5-38 Configuration
(CISHER”)
5.8.5
Function FCODE Option
NO
Default
Value
output 115
Disabled
0 0
Signal Feedforward enabled, Al3
1
Processing
Feedforward enabled, Al4
2
Tracking, Output DI (Al4)
3
Tracking, Signal Selector (Al4)
4
Min selection enabled
5
Max selection enabled
6
Use FCODE 11 to set the amplification in the range of 0 to + 9.99.
Function Parameters
FCODE Range Unit
Increment Default Selected
Value Value
Feedfor- Gain 11
Sk999 - 0.1
0
ward
Output Signal Tracking
There are two types of output tracking functions selectable with the
DPRSOO controller using FCODE 115. While both functions deal with
the output signal to the final control device, one option is discretely
selectable through Dll while the other option is High/Low Signal
selectable.
Option 3: “Output Tracking”
Discrete
Switching+
Signal
Option 4: “Signal Selection”
T
P
DPRSOO
0
Remote
Analog __I
output
Signal
Change 1 -September 1991