Configuration 
5-19 
5.6.3.2  Process  Value  Alarms 
DO3  and  DO4  outputs  can  indicate  only  one  of  the 
following:  sensor  status,  PV  alarms,  setpoint 
deviation  alarm  limits,  or  setpoint  ramping. 
The  use  of the  PV  monitoring  function  precludes 
the  use  of  the  Min/Max  selection  function  for  both 
the  PV  and  remote  setpoint. 
There  are  five  alarm  options  and  two  possible  limits  for  process  value 
alarms.  Each  alarm  option  uses  the  same  limits.  Use  FCODE  103  to 
set  type  of alarm. 
Function  FCODE  Option 
No  Default  Selected 
V&e  V&&? 
PWXZ?SS  103  Disabled  0  0 
WlX  High/low  alarm  1 
Alarm  High  alarm  only  2 
Low  alarm  only 
3 
High/High-High  alarm  4 
Low/Low-Low  alarm 
5 
Process  value  alarms,  setpoint  deviation  alarms, 
sensor  status,  and  setpoint  ramping  all  use  DO3 
and  D04,  and  are  mutually  exclusive.  If  more  than 
one  of these  functions  is  set  at  a  time  the  display 
indicates  ERROR  during  configuration. 
The  following  table  shows  which  outputs  carry  the  selected  alarms. 
Only  one  of  the  indications  can  be  on  at  any  given  time. 
Change  2  -July  1992 
UMtIi:DPR900:9147