5-26 
Configuration 
(FISHER”] 
Function  Parameters  FCODE  Range  Unit  Increment  Default  Selected 
V&N?  Value 
Extra  Setpoint  value  12  MSIS. 
a”Y 
1  digit  Min 
Internal  Range 
Setpoint 
FCODE  12  defaults  to  the  lower  measuring  range 
value  as  set  in  FCODE  24. 
Function 
FCODE  OptIon  NO  Default  Selected 
V&e 
Value 
Automatic  142  Disabled 
1  1 
Setpoint  Switches  to  remote  setpoint  2 
Switchmg  Switches  to  extra  internal  setpoint  3 
The  ESP  is  functionally  a  RSP.  The  R  button  LED  remains  lit  when 
this  setpoint  is  active,  as  a  reminder  that  manual  setpoint  entry  is  not 
possible.  If  FCODE  142  is  set  to  Option  3,  switching  to  extra  internal 
setpoint  enabled,  the  extra  internal  setpoint  is  displayed  in  the  remote 
mode.  Simply  press  one  of  the  green  setpoint  increase/decrease 
buttons  to  view  the  current  digital  value  of  ESP  when  active. 
The  local  setpoint  can  be  made  to  track  both  ESP  and  RSP.  Switching 
can  be  done  manually  or  using  a  discrete  input  signal.  FCODE  140  is 
used  in  this  case,  however  the  ESP  replaces  the  RSP  in  the 
description.  Select  the  LSP  tracking  option  using  FCODE  140. 
Function 
FCODE  Option  NO  Default  Selected 
Value 
Value 
Setpornt 
140  Disabled  1  1 
Tracking  Tracks  remote  setpomt  (RSP/ESP)  2 
WY 
Tracks  PV  ,n  Manual 
3 
The  manual  button  overrides  both  the  remote  and 
extra  internal  setpoints,  when  they  are  active. 
When  the  controller  is  in  the  manual  mode,  the 
local  setpoint  can  be  set  but  is  not  in  use. 
UM61:DPR900:9102  Change  1 -September  1991