EasyManua.ls Logo

Fisher DPR900 - Bargraph Displays Usage

Fisher DPR900
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Controls and lnd;cators
3-5
3.3
3.3.1
100
90
60
70
60
50
40
30
20
10
n
PV % SP
Bargraph Displays
Process Values
The process value bargraph displays the process value or any
deviation alarm limits which may have been set. The two types of
alarm limits are high/low and deviation alarms. Only one type may be
present at a time.
High/low alarms are indicated by a brighter bar for each alarm
setting. A maximum of two alarm points may be set. The upper and
lower bright bars indicate the high-high and low-low alarms. If the
alarm points are separated by less than 2.5%, only one bar is
shown.
Deviation alarms are shown in the same manner as high/low alarms.
The alarm limits however, are set relative to the setpoint and change
when the setpoint changes. If the alarm limits are separated by less
than 2.5%, only one bar is shown.
The display at the left indicates a PV low setpoint deviation alarm of
25%. The display at the right indicates PV alarms set at 82 and 50%.
Setpoint
The setpoint bargraph normally displays the setpoint value. If the
point ramp is in operation, the setpoint final value is shown as a
brighter bar during the ramp operation period.
In the display shown, the final operator set ramped setpoint is 87%,
while the current setpoint is 75%.
Output Signal
The reading of the output signal display is dependent on the mode of
operation selected.
May 1991
lJM6.1:DPR900:9102

Related product manuals