Configuration
5-9
The user must press the M button to control the
output signal manually even though a discrete
input may have switched the controller to manual
mode. The manual mode yellow increase
/decrease buttons only light after pressing the M
button to indicate that manual control is possible.
When output signals are remotely controlled,
pressing the M button does not light these two
buttons, indicating that they are not locally
adjustable.
Use FCODE 110 to select the function and the input signal line, Dll or
Dl2.
Function
FCODE
Option NO Default Selected
VallK? Value
EXtWlal 110 Disabled 0 0
A/M Track AutolManualmrack switching via DII 1
Switching Auto/Manual~rackswitchingvia D12 2
-I
Use FCODE 111 to select the external remote/local switching option.
Function FCODE
Option NO Default Selected
V&e Value
EXtfXflal
111 Disabled 0 0
WL Remote/Local switching via DII 1
Switching
Remote/Local switching via Dl2 2
Use FCODE 112 to select the option for forced control of the output
signal via Dll or Dl2.
Function FCODE Option
No Default Selected
Value V&B
Forced 112 Disabled 0 0
output
Dll, applies in Auto/Manual 1
Control Dl2, applies in Auto/Manual 2
Dll, applies in Auto only
3
Dl2, applies in Auto only 4
While the external discrete switching signal is
active, it is not possible to return to the auto mode
manually.
Change 1 -September 1991
lJM6.1:DPR900:9102