5.2. Discrete Inputs Register 2 [read]
address Name Description unit Type factor
0 System On/O true = On
10 Pump On true = active
14 Remote control true = active
18 Collection
disturbance
true = active
22 Flow exceeded true = active
26 Flow below limit true = active
30 Temperature
exceeded
true = active
34 Pressure exceeded true = active
38 Pressure below true = active
42 Filter outdated true = active
46 Filter full true = active
5.3. Single Coils Register 5 [write]
address Name Description unit Type factor
12 System On/O 1 switching
pulse
=
Mode
switch
16 Activate remote
control
20 Normal operation
On/O
24 Continuous
operation on/o
28 confirm new filter
32 Fault Unlock
30 We reserve the right to change the design and technical specifications of our products.