5.7. Fault contact SFC
The Sideflow Clean Pro can forward faults to the building management system.
The active fault message can be forwarded to the building management system by a
direct connection to terminal A6 (NO) and terminal A6 – C.
During normal operation without fault message, contact A6–C and contact A6–NO are
closed, contact A6-C to A6-NC is open.
In case of an active fault message or an interrupted
Power supply, contact A6-C and contact A6–NO are opened and contact A6–C is
closed with contact A6–NC.
33
Sideflow Clean Pro
> Modbus-RTU
ENG