5.4. Input Register 4 [read]
address Name Description unit Type factor
50 PMW power pump % Signed 16-
bit
(Big Endian)
x 0,1
54 Operating mode 1 = Normal
operation,
2 = Duration
operation
58 Filter loading % x 0,1
62 temperature °C x 0,1
66 Pressure before
filter
bar x 0,01
70 Pressure after filter x 0,01
74 Flow sensor l/min
78 Remaining days
of continuous
operation
Days
82 Remaining time
continuous
operation
secondary 32-bit
floating
point
(Big Endian)
86 Quantity counter
day
m
90 Quantity counter
week
94 Quantity counter
month
98 Quantity counter
year
102 Quantity counter
total
106 Amount of water
per filter
31
Sideflow Clean Pro
> Modbus-RTU
ENG