6.7.7. Function 7 - Delay
Value: Seconds.
If more than one fill is selected in Function 6, enter the required delay between the fills.
The value of the delay can range between 0.0 and 25.5 seconds, with intervals of 0.1
second.
Function 7 is only active while filling is carried out and only if more than one fill has been
entered in Function 6.
6.7.8. Function 8 - Completed fills
Value: Number.
Nothing can be entered in this function, as it only displays the number of fills completed since
the latest reset of the function.
To reset this function, press the <C> key.
6.7.9. Function 9 - Specific gravity
If the product has another specific gravity than the usual 1.0 (Water), then it is entered here.
The default value is 1.0000 g/ml.
Changing specific gravity should be followed by a calibration .
6.7.10. Function 10 - Output rate
Value: Number of fills per time unit.
Nothing can be entered in this function as it only displays how many fills the system carries
out per time unit.
The time unit can be changed between hours and minutes in Function 70. See also
information about Function 70.
The function operates as follows: The MC12 records the precise time between two fills via
the built-in clock, and calculates the number of fillings per time unit.
The display is updated at the completion of each fill.
The function can be called up for viewing, but it cannot be reset and values cannot be
entered in this function.