What to do if the Flow Safe F7000 Control Unit main valve leaks through the outlet?
- JJames MosleyAug 11, 2025
If the main valve of your Flow Safe Control Unit is leaking through the outlet, it could be due to damage or contamination on the piston seat, main valve nozzle, piston seal/sealing surface, or lower liner seal/sealing surface. Disassemble the valve, remove the piston and liner, and examine the seat, seals, and sealing surfaces under magnification. If damaged, replace with new parts; if contaminated, clean and reinstall. Alternatively, the dome might not be loading properly through the pilot.