What to do if the valve position reading is not accurate on my Flowserve Logix 3800zb?
- OosmithAug 3, 2025
If the valve position reading of your Flowserve Industrial Equipment is not accurate, there are several potential causes: * The stroke might not be calibrated: Perform a Stroke calibration (Quick-Cal). * The analog input might not be calibrated: Perform an Analog input calibration. * Tight shutoff could be active: Verify Tight Shutoff settings. * Custom characterization or soft stops might be active: Verify custom characterization or soft-stop limits.